Figure 11.14 shows the voltage waveform of the 380 V busbar during transfer from grid-connected mode to islanded mode,
Figure 11.15 shows the
current waveform of the PCS during transfer from grid-connected mode to islanded mode,
Figure 11.16 shows the current waveform of the PV inverter during transfer from grid-connected mode to islanded mode, and
Figure 11.17 shows the voltage trend during transfer from grid-connected mode to islanded mode and then to grid-connected mode. During the transfer from grid-connected mode to islanded mode, due to loss of support from the macrogrid, the circuit breakers of the main incoming line and unimportant
loads open quickly, and instantly the microgrid loses power, the PV system quits service, and the ESs switch from grid-connected mode to islanded mode. Five to 10 seconds later, the microgrid enters the islanded mode, and the busbar voltage and system frequency restore to normal level. As such, after separating from the macrogrid, the microgrid experiences a short-time outage before entering the islanded mode.