4.9 EXCITATION

The field voltage and current may be specified by a dc generator driven by a motor or by the shaft a of turbine generator. These units are called exciters and the complete voltage controls system, including error detection and various feedback loops is called an excitation system or an automatic voltage regulator (AVR).

4.9.1 Exciter system block diagram

The following figure represents a simplified excitation system. The control input is Vref. Then Vref is raised while generator terminal voltage |Va| initially remains the same. Ve goes up, VF increases and |Ve| tends to increase.

A new equilibrium reached with a higher |Va|. If |Va| changes because of a change in load, we also get a correcting action (See Fig. 4.12)

images

Fig 4.11 Simplified excitation system

4.9.2 IEEE Type-1 excitation model:-

For more quantitative results the standard model is IEEE type-1 model whose block diagram is as shown below.

images

Fig 4.12 Block diagram representation of IEEE Type-1 excitation system and generator

All the variables we are considering are in p.u. In this case, gain of measurement block is unity in the steady state. The amplifier gain is typically in the range of 25 to 400. Ta is typically in the range of 0.02 to 0.4 sec. and VRminVRmax. Within the limits, the gain in the linear zone is 1. Typical range of feedback again KF is 0.07 to 0.1 and feedback time constant TF is in the range of 0.35 sec to 2.2 sec.

The open-circuited voltage of a DC generator is proportional to the product of speed times the air gap flux per pole. The flux is a non linear function of the dc generator field current because of saturation effects in the magnetic circuit. When the loading of the generator by ac generator field winding is considered, we get a load saturation curve. The air-gap line is tangent to the lower (approx) linear portion of the open circuit saturation curve. f (VF) measures the departure of load-saturation curve and where k is the slope of the air gap line from the field circuit of the dc generator

images
images

Fig 4.13 Exciter load saturation curve

images

Where uR = output of the amplifier and R, I λ are resistance, current and flux linkage of the DC generator field winding connected across the amplifier terminals.

Next, assume that dc generator output voltage uF is proportional to the dc generator air-gap flux, which in turn is proportional to λ and

 

VFβλ                                (4.23)

Therefore, substituting Eq(4.22) and (4.24) in (4.23), we get

images

Multiplying by images we get

images

The factor s(UF) accounts the load saturation curve from the air-gap line.

Example 4.1

A 200 MVA synchronous generator operates at 50 Hz under nominal loading conditions. If an additional load of 50 MW is suddenly applied, assuming a time lag of 0.65 sec in the speed governor system which delays the opening of steam valve to meet the additional demand, determine the frequency of the system before the system flow commences. Given that H = 7 MW-sec/MVA of generator capacity.

Solution:

images

From the given data

 

  f 0 = 50Hz
W 0K.E = H × Pr

where H is the inertia constant in MW-sec/MVA

Pr is the generation rating in MVA

= 7 × 200 = 1400 MW- sec (or)MJ

The new kinetic energy

 

            WK.E = W 0K.E − [Energy lost due to the additional load]

                    = 1400 − [50MW × 0.65 sec]

                    = 1367.5 MJ

The new frequency of the system before steam flow commence is

images

Example 4.2

An inductive load Z = R +jX is connected across a supply voltage V. How would a 2 percent drop is frequency affect the real load, if the load is assumed to have a power factor of 0.8 [A.U; Dec 2004]

Solution:

We know that P + jQ = VI* (or) PjQ = V*I

images

Multiplying with complex conjugate

images

Differentiate w.r.t ‘f

images

We know that,

images

Substituting the above expression in the images equation

images

Now a 2% drop is frequency is

            change in ‘P’ = −0.72(0.02)

                                = −0.0144 = −1.44%

                                = 1.44%increase in load(Due to − ve sign).

Therefore, a 2% drop in frequency increases the load by 1.44

Example 4.3

An inductive load of Z = R +jX is connected across a supply ‘V’. By how many percent will the real drop be if the voltage is reduced by 5?.

Solution:

 

From Example 4.2,

images

Rearranging images

Change in real power = 2× (change in voltage)

Now, for a 5% drop in voltage,

change in ‘P’ = 2 × 0.05 = 0.1 = 10%

Therefore a 5% drop in voltage reduces the load by 10%

Example 4.4

Considering Example 4.1, if a load of 50 MW is suddenly removed instead of adding for the same system parameters, determine the frequency of the system before the steam flow begins to decrease.

Solution:

 

From Example 4.1 we know that,

images

but f 0 = 50Hz

W 0K.E = H × Pr = 7 × 200 = 1400 MW sec

The new kinetic energy

            WK.E = W0K.E + [Energy gained due to decrease in load]

                    = 1400 + [50 MW × 0.65 sec]

                    = 1432.5 MW sec

The new frequency of the system before steam flow start to decrease: is

images
..................Content has been hidden....................

You can't read the all page of ebook, please click here login for view all page.
Reset
3.128.199.138