2.3 DERIVATION OF THE TRANSMISSION LOSS FORMULA

This section presents an easier method for derivation of the transmission loss formula. Fig. 2.1 represents two generating units 1 and 2 feeding a number of loads, totaling to IL through a large transmission network. Out of the many branches within the network, consider a branch (any three-phase transmission line) designated as b.

images

Fig 2.1 Network with two generators feeding a large number of loads, and any one branch b of network

Let the switch in Fig.2.1(a) be open. Then the total load current IL is supplied by generator 1 only. With generator 1 acting alone, the current in the line b is Ib1 whereas the generator current is I1.

Now define current distribution factor ab1 as:

images

Similarly, let the switch in Fig.2.1(b) be open and the total load current IL be supplied by generator 2 only. With generator 2 acting alone, the current in the line b is Ib2 whereas the generator current is I2.

Now define current distribution factor ab2 as:

images

When both the generators are connected to supply the load current, the current through the branch b i.e. Ib can be obtained by applying the principle of superposition as:

 

Ib = Ib1 + Ib2 = ab1I1 + ab2I2                    (2.12)

The current distribution factors are taken as real numbers owing to the following assumptions:

  1. The phase angle of all load currents are the same.
  2. The ratio X/R for all transmission lines in the transmission network is the same.
images

Where θ1, θ2 are the phase angles with respect to a common reference.

 

I1 = |I1|cosθ1 + j|I1|sinθ1
I2 = |I2|cosθ2 + j|I2|sinθ1

 

From Fq.(2.12).

 

Ib = ab1I1 + ab2I2                            (2.13)
images

Now, let

P1, P2 = 3-Phase real power outputs by generators 1 and 2 respectively.

I1 = (P1/images × V1cosθ1); I2 = (P2/images × V2cosθ2)

cosθ1, cosθ2 = power factors at generator ends 1 and 2 respectively

V1, V2 = bus voltages at generator ends 1 and 2 respectively

Rb is the resistance of branch b

Let k be the number of branches in the transmission network.

Now, the total transmission loss in the entire network is given by

images

Substitute I2b from Eq. (2.14) in Eq.(2.15)

images

Substituting I1 and I2

images

The above loss equation in terms of B-coefficients can be written as:

 

PL = B11P12 + B22P22 + 2B12P1P2                    (2.16)

where,

images

The terms B11, B12 and B22 are called loss coefficients or B-Coefficients. The units of B-coefficients are in MW–1 when the voltages are in KV and branch resistances in ohms.

B-coefficients for multi-machine power systems.

Let Eq. (2.16) be extended for a power system with ng number of generators. Total transmission losses in the system are:

images

Where Bmn are elements of the S-Matrix.

Diagonal terms in the B-Matrix:

images

Off-Diagonal terms in B-Matrix:

images

Expanding Eq.(2.17).

 

P1 = B11P12 + B22P22 + B33P33 + … + 2P1P2B12 + 2P2P3B23 + …    (2.20)

In the matrix form of Eq.(2.20),

images

In the condensed form, Eq.(2.21) can be written as

 

PL = P B PT                                (2.22)

Example 2.1

A four-bus power system network is shown in Fig 2.2(a).

images

Fig 2.2(a)

Currents flowing in the lines are marked and are given as:

 

                      Ix = 4-j 1 p.u;    Iy = 2-j 0.5 p.u;
Iz = 3-j 0.75 p.u

 

The branch impedances are:

 

        Zx = 0.01+j 0.04 p.u;
        Zy = 0.015+j 0.06 p.u
and Zz = 0.01+j 0.04 p.u

 

Take voltage at bus 1 as images p.u and base MVA as 100. Compute B-coefficients of the network.

Solution:

 

The load currents at bus 2 and bus 4 are:

 

    IL1 = Ix + Iy = 6 − j 1.5 p.u
IL2 = Iz = 3 − j 0.75 p.u

 

Determination of current distribution factors:

Step-1: Let us assume that the total load be supplied by generator G1 alone.

images

Fig 2.2(b)

IL = Total load current = IL1 + IL2 = 9 – j 2.25 p.u referring to Fig.2.2(b), the current distribution factors can be determined as below.

images

Step-2: Let the total load be supplied by generator G2 alone.

Referring to Fig 2.2(c), the current distribution factors are computed as shown below:

images

With the help of Fig. 2.1(a), the bus voltages can be determined as follows:

images

The generator currents and voltages are:

images

The phase angle at the Generator-1 terminal Φ1 = 0° – (–14.03°) = 14.03°

images
images

Fig 2.2(c)

The phase angle at the Generator-2 terminal Φ2 = –6.115 – (–14.03°) = 7.915°

The plant on generator power factors are:

 

cos φ1 = 0.97;
cos φ2 = 0.99

 

The current phase angles at G1 and G2 terminals are:

images

Therefore, cos(δ1δ2) = cos 0° = 1 (i.e. I1 and I2 are in phase)

images

On a 100MVA base the loss coefficients can be obtained by dividing the p.u values by 100

images

Note:

The following assumptions are made for simplifying the procedure of computing B-coefficients.

  1. All load currents have the same phase angle with respect to a common reference. It can be seen in Example 2.1, that

    IL1 = 6 – j 1.5 = 6.18 imagesp.u and

    IL2 = 3–j0.75 = 3.092 images p.u. The phase angle of both the load currents is the same i.e., 14°.

  2. The X/R ratio for all branches of the network are the same. It can be seen in Example 2.1 that the X/R ratio of the branches x, y and z are the same and its value is 4.

    The above two assumptions are essential to make the current distribution factor as real numbers, rather than complex numbers.

  3. Voltage magnitudes at the generator buses remain constant.
  4. The phase angles between generator bus voltages and currents for all the generating units are the same. In other words, power factor at each plant remains constant.

    It can be seen in Example 2.1 that the Generator-1 current I1 = 4.123 images and Generator-2 current I2 = 5.153 images That is, δ1 = δ2 = – 14.03°.

Example 2.2

Consider the power system shown in Fig.2.3.

images

Fig 2.3 A Two Generator Power System

The power loss equation is represented as PL = B11P21 + 2B12P1P2 + B22P22. All the terms in the equation for PL are standard notations. The resistances of lines are marked in the figure. Compute the B-coefficients in terms of resistances.

Solution:

 

From the figure,

 

IL = I3 = I1 + I2                            (1)

where,

images

The total power loss in the system is:

 

PL = 3(I12R1 + I22R2 + I32R3)                    (2)
images

Simplying the above,

images

Representing the above in the standard form,

 

PL = B11P12 + 2P1P2B12 + B22P22

where

images

and

images

Example 2.3

The power system in Example 2.2 is modified as shown in the Fig. 2.4. Compute the B-coefficients

images

Fig 2.4 Power system with two generators

Solution:

 

Comparing Fig.2.3 and Fig.2.4, it can be understood that R3 = 0 in this case. Substituting R3 = 0,

images

The modified loss equation is

 

PL = B11P12 + B22P22

Example 2.4

The power system in the Example 2.2 is modified as shown in the Fig 2.5. Compute the B-coefficients.

images

Fig 2.5 Load is connected near Generator-2

Solution:

 

In this case, the load is connected near Generator-2.

By substituting R2 = R3 = 0, the B-coefficients are:

images

The modified loss equation is:

images

Any amount of power supplied by G2 will not produce losses.

..................Content has been hidden....................

You can't read the all page of ebook, please click here login for view all page.
Reset
18.218.171.212