of the generator’s current rating. This standard hinges upon
generator design and operation. “The output of the generator
must be protected from overloads. The circuit breakers, fuses,
or other acceptable overcurrent protective means should be
able to prevent overloading of the conductor.” [445.12(a)]
According to Article 445.18, generators require a disconnect
device unless they can be shut down easily and do not operate
in parallel with another voltage source.
Point-of-Utility Connections
Utility grid-tied PV systems are connected through the customer’s service
entrance section. This is known as the SES in almost every situation. Utility-
owned and developer-owned PV systems attach on dedicated PV service
entrances. These SESs are often set up for the project independent of any load
other than that of the grid. The NEC allows this. Article 230.82(6) gives the par-
ticular requirements needed for connections. Customer-owned PV systems
couple through a breaker. Those PV systems must always have an appropriate
means of disconnecting.
The place where the PV system connects to the utility service is called the
point-of-utility connection. Locate the point-of-utility connection at the main
distribution panel board. The easiest way to do this is typically to place the
inverter output breaker on the customer load side of the main breaker in the SES.
This will feed the house loads first with any excess being sent out to the grid. The
inverter output must have a circuit breaker or fuse in the distribution panel board.
The circuit breaker or fuse must be appropriately labeled. When connecting the
inverter to the circuit breaker, use appropriate techniques to secure the enclosure.
Make sure to follow NEC Article 705.12, which requires that
The enclosure be secured through a reserved circuit breaker or its own fuse
on the disconnecting means.
Overcurrent device amps providing power to the conductor be no greater
than the conductor’s amps.
Point-of-utility connection be on the line part of all the ground-fault
defensive mechanisms.
All mechanisms with overcurrent devices be marked to
warn about power supply.
Optional Standby System Panels
According to NEC Article 702.7, optional standby system
panel boards have to be labeled. They are labeled to warn
workers that an inverter supplies current into the panel board.
[690.10(c)]
NOTE
PV systems with backup generators use
a disconnect to separate the generator
from the rest of the PV system in the
case of repairs and maintenance.
NOTE
Typically, Article 690.10 is for
standalone PV systems, but it can be
applied to grid-tied PV systems with
backup batteries. The battery backup
system acts as a standalone PV system
in instances where the power is out.
CHAPTER 7 PV Technology—Cells, Panels, Arrays, Balance of System, and Inverters 171