through the owner’s manual for each piece of equipment.
Make sure the plan does not cause a conflict with warranties
or component design.
Wiring
When you are ready for wiring, calculate wire lengths from
the PV arrays to the combiner and inverter. Select the correct wire size, as per
NEC requirements, and upsize for a 1 percent or less loss for a high-performing
system. Use maximum overcurrent calculations for each circuit as the basis for
wire size, and double-check for accuracy at the site. (A circuit consists of the wire,
switches, fuses, etc., that attach the load to the power source. The load is the
amount of energy used by any electrical appliance at a given time; or sometimes
the appliance itself is referred to as a “load.”) You must always double-check the
ampacity for array circuits. This also includes checking for the ampacity range for
module-to-combiner wires.
Label the maximum fuse rating. You should always run wires at least 25 feet
between modules to the combiner. Make sure the wire length from the combiner
to the inverter is at least 75 feet. Then calculate the wire distance between the
inverter and main service panel.
PV Components and Batteries
The following basic steps should be taken when installing PV components and
batteries:
1. Make certain the main service panel bus bar is of sufficient size and rating to
house the PV breaker and PV load.
2. Purchase and install a new main service panel, and downsize the main
breaker, if appropriate, or the PV system.
3. Determine which circuits are critical in PV systems that have a critical load
subpanel (battery standby system).
4. Check to see if multi-branch circuits can be wired to 120 VAC standby
systems.
5. Look at the loads connected to the standby power system to see if the system
can handle the actual power consumption and daily usage in standby mode.
6. Connect the standby power systems into a separate subpanel from
the inverter.
7. Measure the standby system’s energy usage.
8. Figure out the battery capacity for uninterrupted power.
9. Choose a storage battery system that meets the customer needs and also has
maintenance-free batteries with absorbed glass mat (AGM) construction.
10. Do not use untested batteries.
11. Place battery cabinets in a cool place away from the sun.
TECH TIPS
Pay close attention to wire size.
Smaller wires may cause voltage drops.
54 ADVANCED PHOTOVOLTAIC INSTALLATIONS