Equipment Grounding
Equipment grounding conductors should be a bare wire or a green wire. [NEC
690.41] They need to handle the highest current that could flow through the cir-
cuit. [NEC 690.41–690.44]
PV Module Grounding
Article 690.5 discusses grounding and fault protection:
Use a single ground point.
Ground one conductor (> 50 V).
Ground the neutral wire of a three-wire system.
Safety Hints for Testing a PV System
Before testing any PV system, know the answers to the following questions:
What are the system voltages?
What are the system currents?
How many circuits are there?
What are the overcurrent devices?
Where are the overcurrent devices?
Where is the system disconnected?
Where is the safety equipment located?
After those questions are answered, then it is time to go to the PV system site.
When at the PV system site, always take these precautionary measures:
1. Take off any jewelry.
2. Walk around the system and document any dangerous circumstances—write
them down and take pictures.
3. Locate the inverter and battery.
CODE
NEC 2011, 200.6 (6)
A single-conductor, sunlight-resistant, outdoor-rated cable used as a grounded conductor in
photovoltaic power systems, as permitted by 690.31, shall be identified at the time of installation
by distinctive white marking at all terminations.
Reprinted with permission from NFPA 70
®
, National Electrical Code
®
, Copyright© 2010, National Fire
Protection Association, Quincy, MA.
CHAPTER 2 Essential Safety Practices for Designing and Installing PV Systems 41